A pneumatic wafer butterfly valve combines a wafer-style butterfly valve body with a pneumatic rotary actuator for automated shutoff and control in HVAC systems, water treatment plants, industrial piping and process automation. It responds to 4-20 mA or on/off signals from a PLC or DCS, providing fast, reliable and repeatable operation without manual labor.
We manufacture pneumatic wafer butterfly valves in stainless steel CF8 (304) and CF8M (316) as our standard range. Ductile iron (GGG50), cast iron (GG25) and carbon steel (WCB) bodies are available for budget HVAC and water treatment projects. Sizes DN40–DN600 (NPS 1½″–24″), PN10–PN16, ANSI 150#, disc in SS304/SS316 with EPDM/NBR/Viton seat. Available with spring return (fail-safe open or close) or double acting actuator, with optional solenoid valve, positioner, limit switch and air filter regulator.
Every valve is shell and seat pressure tested per API 609 before shipment, and the actuator is cycle-tested for leakage and operation. MOQ 1 piece, 7–15 days delivery, ISO 9001:2015, shell and seat pressure tested. For manual operation, compare our manual wafer butterfly valve. For food-grade service, see our pneumatic sanitary butterfly valve. For electric actuation without compressed air, see our electric actuated valve. get a detailed quotation for your project.
The main advantage of a pneumatic wafer butterfly valve over a manual valve is automation. The pneumatic actuator allows remote operation via PLC/DCS, reducing labor costs and improving process consistency. The spring return actuator provides fail-safe operation in case of air supply failure — valve closes or opens automatically to protect the system. In automated pump stations, pair it with a wafer dual plate check valve to prevent reverse flow, and protect equipment with a Y-strainer. Complete the automated system with matching stainless steel flanges.
We directly serve EPC contractors and valve distributors in Southeast Asia (Indonesia, Malaysia, Thailand, Vietnam) and the Middle East (Saudi Arabia, UAE, Qatar, Kuwait).
🌏 Southeast Asia & Middle East Market Notes
Indonesia & Malaysia palm oil mills: Spring return (fail-close) with Viton seat is standard for sterilizer and steam condensate lines — valve closes automatically on air supply failure to protect the process.
Saudi Arabia & UAE desalination plants: Double acting with 316L body, IP67 limit switches and 24V DC solenoid valves integrated into the BMS. Hot desert ambient temperature up to 55°C — we use high-temperature Viton seals in the actuator.
Vietnam & Thailand HVAC: Double acting 230V AC solenoid, EPDM seat, integrated into building automation systems for chilled water balancing. Modulating version with 4–20mA positioner available for VAV systems.
Not sure which actuator size or configuration you need? Send us your medium, pressure and fail mode.
Get Free Sizing Report →Manual vs Pneumatic vs Electric Actuation
| Feature | Manual (Lever/Gear) | Pneumatic | Electric |
|---|---|---|---|
| Stroke time | 10-60 seconds | 1-5 seconds | 15-60 seconds |
| Remote control | No | Yes (PLC/BMS) | Yes (PLC/BMS) |
| Fail-safe on air/power loss | Stays in position | Spring return: closes/opens automatically | Stays in position (battery backup optional) |
| Explosion proof | N/A | Yes (Ex-proof version) | Expensive (Ex-rated motor) |
| Cost (DN100) | Lowest | ~2-3× manual | ~3-5× manual |
| Best for | Isolation, infrequent operation | Automated shutoff, fast cycling, hazardous areas | Remote location without compressed air, modulating control |
| Our product | Wafer Butterfly Valve | Pneumatic Wafer Butterfly Valve | Electric Actuated Valve |
Technical Specifications
| Size Range | DN40 – DN600 (NPS 1½” – 24″) |
| End Connection | Wafer type, fits between DIN EN 1092-1 PN10/PN16 / ANSI B16.5 Class 150 / JIS 10K flanges |
| Body Material | CF8M (316) / CF8 (304) — standard; GGG50 / GG25 / WCB available on request |
| Disc | SS304 / SS316 (optional Nylon or EPDM coated) |
| Seat | EPDM / NBR / Viton (FKM) |
| Actuator Type | Pneumatic rack & pinion, spring return or double acting |
| Air Pressure | 4 – 8 bar (60 – 120 psi) clean dry compressed air |
| Pressure Rating | PN10 – PN16 / ANSI 150# |
| Temperature Range | -10°C ~ +110°C (EPDM) / -20°C ~ +80°C (NBR) / -20°C ~ +180°C (Viton) |
| Actuator Body | Extruded aluminum anodized, epoxy powder coated; NAMUR mounting interface |
| Options | Solenoid valve (NAMUR), positioner (4-20mA), limit switch box (IP67), handwheel override, air filter regulator |
| Applicable Media | Water, oil, gas, HVAC, water treatment, process automation |
| Testing | shell & seat pressure test per API 609 / EN 593; bubble-tight acceptance per API 598; actuator cycle test (1000 open/close cycles) |
| Material Certificates | EN 10204 3.1 MTC per heat, included with shipment |
| Standard | API 609, EN 593, face-to-face per EN 558 Series 20; ISO 5211 mounting flange |
Dimension Table — EN 558 Series 20 Wafer (Valve Body, mm)
L = face-to-face length (short wafer pattern). ΦD = matching bolt circle of DIN EN 1092-1 PN16 pipe flanges. n-Φd = through-bolt holes. ANSI B16.5 Class 150 / JIS 10K drilling available on request.
| DN | NPS | L (mm) | H1 (mm) | ISO Top Flange | Mating PN16 ΦD (mm) | Mating PN16 n-Φd |
|---|---|---|---|---|---|---|
| 40 | 1½” | 33 | 70 | F04 | 110 | 4-Φ19 |
| 50 | 2″ | 43 | 70 | F05 | 125 | 4-Φ19 |
| 65 | 2½” | 46 | 77 | F05 | 145 | 4-Φ19 |
| 80 | 3″ | 49 | 92 | F05 | 160 | 8-Φ19 |
| 100 | 4″ | 52 | 105 | F07 | 180 | 8-Φ19 |
| 125 | 5″ | 56 | 120 | F07 | 210 | 8-Φ18 |
| 150 | 6″ | 56 | 134 | F07 | 240 | 8-Φ23 |
| 200 | 8″ | 60 | 171 | F10 | 295 | 12-Φ23 |
| 250 | 10″ | 68 | 204 | F12 | 355 | 12-Φ27 |
| 300 | 12″ | 76 | 241 | F14 | 410 | 12-Φ27 |
| 350 | 14″ | 89 | 271 | F14 | 470 | 16-Φ27 |
| 400 | 16″ | 102 | 298 | F16 | 525 | 16-Φ30 |
| 450 | 18″ | 114 | 331 | F16 | 585 | 20-Φ33 |
| 500 | 20″ | 127 | 369 | F16 | 650 | 20-Φ33 |
| 600 | 24″ | 154 | 450 | F30 | 770 | 20-Φ36 |
* Valve body dimensions per EN 558 Series 20. Actuator overall height, mounting footprint and torque curve vary by actuator size and brand — contact us for exact actuator mounting dimensions on your valve size.
🧮 Worked Example: Sizing a Pneumatic Actuator for DN150
Project: Automated backwash valve for a multimedia filter in a water treatment plant in Jakarta, Indonesia.
Given: DN150 wafer butterfly valve, water at 30°C, PN10, air supply 6 bar, require fail-close on air failure.
Step 1 — Determine valve torque:
DN150 butterfly valve break torque (EPDM seat, water) ≈ 25 N·m. Running torque ≈ 15 N·m.
Step 2 — Apply safety factor:
For water service, safety factor = 1.5 (future seat friction, debris).
Required actuator output = 25 × 1.5 = 37.5 N·m.
Step 3 — Select actuator:
Spring return actuator at 6 bar provides output torque ≈ 45 N·m (spring closing torque). This is > 37.5 N·m . We choose a SR83 size. Mating flanges: DIN EN 1092-1 PN10, K=240 mm, 8×Φ22 bolt holes.
Step 4 — Select accessories:
Solenoid valve 24V DC (IP65), limit switch box 2× SPDT, air filter regulator 5µm. Handwheel override not required for this application.
⚠️ 4 Common Mistakes When Selecting Pneumatic Butterfly Valves
Mistake 1 — Forgetting safety factor: Actuator output must be ≥ 1.5× valve break torque for water, and 2× for sticky media (oil, slurry). Undersized actuators stall after 6-12 months.
Mistake 2 — Wrong fail mode: For fire protection and steam, you need fail-close (spring closes on air loss). For HVAC freeze protection, you need fail-open. Confirm with the process engineer before ordering.
Mistake 3 — No air filter regulator: Compressed air contains moisture and oil. Without a 5µm filter regulator, the actuator seals fail within 6 months. Always include FRL.
Mistake 4 — Using double acting where spring return is needed: On air supply failure, a double acting valve stays in its last position — this can cause overflow or pump damage. Use spring return for emergency shutoff.
Need Sizing Help or a Quote?
Send size (DN), pressure (PN/ANSI), material (304/316L), seat (EPDM/Viton) and quantity — we reply within 24 hours.
Get Free Quote »Applications
HVAC BMS: Automatic control of chilled water and condenser water circuits, AHU isolation.
Water Treatment: Automated filter backwash, pump stations, distribution networks, RO desalination.
Process Industry: Chemical processing, power plants, food & beverage, pulp & paper.
Fire Protection: Deluge valve control, fire pump header isolation (fail-close).
Quality Control
1. Raw material inspection (spectrometer test for chemical composition)
2. CNC machining & dimensional inspection
3. Shell pressure test (1.5× PN rating, 60 seconds hold)
4. Seat pressure test (1.1× PN rating, bubble-tight acceptance per API 598)
5. Actuator cycle test (1000 open/close cycles) & final inspection
📋 Commercial Terms
Payment: T/T 30% deposit + 70% before shipment; L/C at sight accepted for EPC package orders (MOQ USD 30,000+). PayPal for sample orders.
Warranty: 12 months after shipment for material and manufacturing defects — covers valve casting defects, disc / seat non-conformance, stem leakage, body dimensional non-conformance (face-to-face, flange drilling), actuator stroke failure and solenoid / limit switch non-conformance under rated air supply. Damage from misuse, lack of air filtration (no FRL installed), wrong fail-mode selection by the customer, over-torque adjustment, or field disassembly / re-packing of the actuator by the customer is not covered. Always quote the valve serial number and heat number from the EN 10204 3.1 MTC when raising a claim.
Packaging: Export plywood case; fumigation-free pallet; flange faces and stem protected; actuator in protective plastic bag with transit clip on solenoid.
Shipping Documents: EN 10204 3.1 MTC per heat, API 609 / API 598 hydro & seat test report, actuator cycle test report, packing list, commercial invoice, EN 10204 3.1 MTC on request.
Shipment Port: FOB Ningbo / Shanghai, China; EXW, CIF or DAP available on request.
Third-Party Inspection: SGS / Bureau Veritas / Intertek pre-shipment dimensional, hydro, seat and actuator stroke inspection supported at buyer cost. Factory audit or video inspection available on request.
FAQ
What is the difference between spring return and double acting actuators?
Spring return closes (or opens) the valve automatically when air supply fails — failsafe position. Double acting uses air for both open and close — higher torque, no failsafe, requires air for both directions.
Can you pre-assemble solenoid valve and limit switch on the actuator?
Yes, we mount solenoid valves (NAMUR), limit switch boxes and positioners on the actuator before shipment, so the valve is ready for direct installation on site.
What air pressure is required?
Standard 4–8 bar (60–120 psi) clean dry compressed air. Lower pressure can be accommodated with larger actuator sizes. Always include an air filter regulator (FRL).
Can this valve be used for modulating (throttling) control?
Yes, with an electro-pneumatic positioner (4-20mA signal), the valve can provide proportional flow control in addition to on/off service.
Do you offer explosion-proof (ATEX) actuators for hazardous areas?
Yes, explosion-proof solenoid valves and limit switch boxes with ATEX certification are available for chemical, oil and gas applications.
Can the valve be operated manually if compressed air fails?
Yes. We recommend adding a handwheel override (manual gearbox) for DN100 and above. This allows operators to manually rotate the disc during air supply maintenance.
What is the lead time and MOQ?
MOQ is 1 piece. Standard configurations ship in 7–15 days. Custom actuator combinations (Ex-proof, positioner, special voltage) or large sizes take 25–35 days.
What is your warranty period?
We provide a 12-month warranty after shipment for material and manufacturing defects. This covers valve casting defects, disc / seat non-conformance, stem leakage, body dimensional non-conformance, actuator stroke failure and solenoid / limit switch non-conformance under rated air supply. Damage from misuse, lack of air filtration (no FRL installed), wrong fail-mode selection, over-torque adjustment or field disassembly by the customer is not covered. Always quote the valve serial number and heat number from the EN 10204 3.1 MTC when raising a warranty claim.
📚 Further reading:
• Electric vs Pneumatic Actuator: Which to Choose?
• Pneumatic Valve Actuators: A Complete Guide
• PN vs Class Pressure Rating: Quick Reference
You May Also Need
Related Technical Guides
Pneumatic Valve Actuators Guide · Electric vs Pneumatic Actuator · Wafer Butterfly Valve Guide
Request a Quote for This Pneumatic Wafer Butterfly Valve
Tell us the size, pressure and quantity you need. We reply within one working day.