Pneumatic Wafer Butterfly Valve | Chuanglan Valve

▲

Pneumatic Wafer Butterfly Valve | Spring Return & Double Acting

Automated butterfly valves that cycle reliably in PLC-controlled systems.

Spring return / double acting pneumatic wafer butterfly valve, DN40–DN600, PN10–PN16, NAMUR rack & pinion actuator

OEM/ODMCustom Manufacturing
ISO 9001:2015Quality Management
Established 2009Valve Manufacturing
7–15 DaysLead Time

* Standard lead time depends on order quantity and destination country. 5–10 days to Southeast Asia, 15–20 days to the Middle East.

✍️ Reviewed by Chuanglan Valve Engineering Team · Last updated Oct 2026 · Follow us on LinkedIn
Pneumatic actuated wafer butterfly valve

A pneumatic wafer butterfly valve combines a wafer-style butterfly valve body with a pneumatic rotary actuator for automated shutoff and control in HVAC systems, water treatment plants, industrial piping and process automation. It responds to 4-20 mA or on/off signals from a PLC or DCS, providing fast, reliable and repeatable operation without manual labor.

We manufacture pneumatic wafer butterfly valves in stainless steel CF8 (304) and CF8M (316) as our standard range. Ductile iron (GGG50), cast iron (GG25) and carbon steel (WCB) bodies are available for budget HVAC and water treatment projects. Sizes DN40–DN600 (NPS 1½″–24″), PN10–PN16, ANSI 150#, disc in SS304/SS316 with EPDM/NBR/Viton seat. Available with spring return (fail-safe open or close) or double acting actuator, with optional solenoid valve, positioner, limit switch and air filter regulator.

Every valve is shell and seat pressure tested per API 609 before shipment, and the actuator is cycle-tested for leakage and operation. MOQ 1 piece, 7–15 days delivery, ISO 9001:2015, shell and seat pressure tested. For manual operation, compare our manual wafer butterfly valve. For food-grade service, see our pneumatic sanitary butterfly valve. For electric actuation without compressed air, see our electric actuated valve. get a detailed quotation for your project.

The main advantage of a pneumatic wafer butterfly valve over a manual valve is automation. The pneumatic actuator allows remote operation via PLC/DCS, reducing labor costs and improving process consistency. The spring return actuator provides fail-safe operation in case of air supply failure — valve closes or opens automatically to protect the system. In automated pump stations, pair it with a wafer dual plate check valve to prevent reverse flow, and protect equipment with a Y-strainer. Complete the automated system with matching stainless steel flanges.

We directly serve EPC contractors and valve distributors in Southeast Asia (Indonesia, Malaysia, Thailand, Vietnam) and the Middle East (Saudi Arabia, UAE, Qatar, Kuwait).

🌏 Southeast Asia & Middle East Market Notes

Indonesia & Malaysia palm oil mills: Spring return (fail-close) with Viton seat is standard for sterilizer and steam condensate lines — valve closes automatically on air supply failure to protect the process.

Saudi Arabia & UAE desalination plants: Double acting with 316L body, IP67 limit switches and 24V DC solenoid valves integrated into the BMS. Hot desert ambient temperature up to 55°C — we use high-temperature Viton seals in the actuator.

Vietnam & Thailand HVAC: Double acting 230V AC solenoid, EPDM seat, integrated into building automation systems for chilled water balancing. Modulating version with 4–20mA positioner available for VAV systems.

Not sure which actuator size or configuration you need? Send us your medium, pressure and fail mode.

Get Free Sizing Report →

Manual vs Pneumatic vs Electric Actuation

FeatureManual (Lever/Gear)PneumaticElectric
Stroke time10-60 seconds1-5 seconds15-60 seconds
Remote controlNoYes (PLC/BMS)Yes (PLC/BMS)
Fail-safe on air/power lossStays in positionSpring return: closes/opens automaticallyStays in position (battery backup optional)
Explosion proofN/AYes (Ex-proof version)Expensive (Ex-rated motor)
Cost (DN100)Lowest~2-3× manual~3-5× manual
Best forIsolation, infrequent operationAutomated shutoff, fast cycling, hazardous areasRemote location without compressed air, modulating control
Our productWafer Butterfly ValvePneumatic Wafer Butterfly ValveElectric Actuated Valve

Technical Specifications

Size RangeDN40 – DN600 (NPS 1½” – 24″)
End ConnectionWafer type, fits between DIN EN 1092-1 PN10/PN16 / ANSI B16.5 Class 150 / JIS 10K flanges
Body MaterialCF8M (316) / CF8 (304) — standard; GGG50 / GG25 / WCB available on request
DiscSS304 / SS316 (optional Nylon or EPDM coated)
SeatEPDM / NBR / Viton (FKM)
Actuator TypePneumatic rack & pinion, spring return or double acting
Air Pressure4 – 8 bar (60 – 120 psi) clean dry compressed air
Pressure RatingPN10 – PN16 / ANSI 150#
Temperature Range-10°C ~ +110°C (EPDM) / -20°C ~ +80°C (NBR) / -20°C ~ +180°C (Viton)
Actuator BodyExtruded aluminum anodized, epoxy powder coated; NAMUR mounting interface
OptionsSolenoid valve (NAMUR), positioner (4-20mA), limit switch box (IP67), handwheel override, air filter regulator
Applicable MediaWater, oil, gas, HVAC, water treatment, process automation
Testingshell & seat pressure test per API 609 / EN 593; bubble-tight acceptance per API 598; actuator cycle test (1000 open/close cycles)
Material CertificatesEN 10204 3.1 MTC per heat, included with shipment
StandardAPI 609, EN 593, face-to-face per EN 558 Series 20; ISO 5211 mounting flange

Dimension Table — EN 558 Series 20 Wafer (Valve Body, mm)

L = face-to-face length (short wafer pattern). ΦD = matching bolt circle of DIN EN 1092-1 PN16 pipe flanges. n-Φd = through-bolt holes. ANSI B16.5 Class 150 / JIS 10K drilling available on request.

DNNPSL (mm)H1 (mm)ISO Top FlangeMating PN16 ΦD (mm)Mating PN16 n-Φd
401½”3370F041104-Φ19
502″4370F051254-Φ19
652½”4677F051454-Φ19
803″4992F051608-Φ19
1004″52105F071808-Φ19
1255″56120F072108-Φ18
1506″56134F072408-Φ23
2008″60171F1029512-Φ23
25010″68204F1235512-Φ27
30012″76241F1441012-Φ27
35014″89271F1447016-Φ27
40016″102298F1652516-Φ30
45018″114331F1658520-Φ33
50020″127369F1665020-Φ33
60024″154450F3077020-Φ36

* Valve body dimensions per EN 558 Series 20. Actuator overall height, mounting footprint and torque curve vary by actuator size and brand — contact us for exact actuator mounting dimensions on your valve size.

🧮 Worked Example: Sizing a Pneumatic Actuator for DN150

Project: Automated backwash valve for a multimedia filter in a water treatment plant in Jakarta, Indonesia.
Given: DN150 wafer butterfly valve, water at 30°C, PN10, air supply 6 bar, require fail-close on air failure.

Step 1 — Determine valve torque:
DN150 butterfly valve break torque (EPDM seat, water) ≈ 25 N·m. Running torque ≈ 15 N·m.

Step 2 — Apply safety factor:
For water service, safety factor = 1.5 (future seat friction, debris).
Required actuator output = 25 × 1.5 = 37.5 N·m.

Step 3 — Select actuator:
Spring return actuator at 6 bar provides output torque ≈ 45 N·m (spring closing torque). This is > 37.5 N·m . We choose a SR83 size. Mating flanges: DIN EN 1092-1 PN10, K=240 mm, 8×Φ22 bolt holes.

Step 4 — Select accessories:
Solenoid valve 24V DC (IP65), limit switch box 2× SPDT, air filter regulator 5µm. Handwheel override not required for this application.

⚠️ 4 Common Mistakes When Selecting Pneumatic Butterfly Valves

Mistake 1 — Forgetting safety factor: Actuator output must be ≥ 1.5× valve break torque for water, and 2× for sticky media (oil, slurry). Undersized actuators stall after 6-12 months.

Mistake 2 — Wrong fail mode: For fire protection and steam, you need fail-close (spring closes on air loss). For HVAC freeze protection, you need fail-open. Confirm with the process engineer before ordering.

Mistake 3 — No air filter regulator: Compressed air contains moisture and oil. Without a 5µm filter regulator, the actuator seals fail within 6 months. Always include FRL.

Mistake 4 — Using double acting where spring return is needed: On air supply failure, a double acting valve stays in its last position — this can cause overflow or pump damage. Use spring return for emergency shutoff.

Need Sizing Help or a Quote?

Send size (DN), pressure (PN/ANSI), material (304/316L), seat (EPDM/Viton) and quantity — we reply within 24 hours.

Get Free Quote »

Applications

HVAC BMS: Automatic control of chilled water and condenser water circuits, AHU isolation.
Water Treatment: Automated filter backwash, pump stations, distribution networks, RO desalination.
Process Industry: Chemical processing, power plants, food & beverage, pulp & paper.
Fire Protection: Deluge valve control, fire pump header isolation (fail-close).

Quality Control

1. Raw material inspection (spectrometer test for chemical composition)
2. CNC machining & dimensional inspection
3. Shell pressure test (1.5× PN rating, 60 seconds hold)
4. Seat pressure test (1.1× PN rating, bubble-tight acceptance per API 598)
5. Actuator cycle test (1000 open/close cycles) & final inspection

📋 Commercial Terms

Payment: T/T 30% deposit + 70% before shipment; L/C at sight accepted for EPC package orders (MOQ USD 30,000+). PayPal for sample orders.

Warranty: 12 months after shipment for material and manufacturing defects — covers valve casting defects, disc / seat non-conformance, stem leakage, body dimensional non-conformance (face-to-face, flange drilling), actuator stroke failure and solenoid / limit switch non-conformance under rated air supply. Damage from misuse, lack of air filtration (no FRL installed), wrong fail-mode selection by the customer, over-torque adjustment, or field disassembly / re-packing of the actuator by the customer is not covered. Always quote the valve serial number and heat number from the EN 10204 3.1 MTC when raising a claim.

Packaging: Export plywood case; fumigation-free pallet; flange faces and stem protected; actuator in protective plastic bag with transit clip on solenoid.

Shipping Documents: EN 10204 3.1 MTC per heat, API 609 / API 598 hydro & seat test report, actuator cycle test report, packing list, commercial invoice, EN 10204 3.1 MTC on request.

Shipment Port: FOB Ningbo / Shanghai, China; EXW, CIF or DAP available on request.

Third-Party Inspection: SGS / Bureau Veritas / Intertek pre-shipment dimensional, hydro, seat and actuator stroke inspection supported at buyer cost. Factory audit or video inspection available on request.

FAQ

What is the difference between spring return and double acting actuators?

Spring return closes (or opens) the valve automatically when air supply fails — failsafe position. Double acting uses air for both open and close — higher torque, no failsafe, requires air for both directions.

Can you pre-assemble solenoid valve and limit switch on the actuator?

Yes, we mount solenoid valves (NAMUR), limit switch boxes and positioners on the actuator before shipment, so the valve is ready for direct installation on site.

What air pressure is required?

Standard 4–8 bar (60–120 psi) clean dry compressed air. Lower pressure can be accommodated with larger actuator sizes. Always include an air filter regulator (FRL).

Can this valve be used for modulating (throttling) control?

Yes, with an electro-pneumatic positioner (4-20mA signal), the valve can provide proportional flow control in addition to on/off service.

Do you offer explosion-proof (ATEX) actuators for hazardous areas?

Yes, explosion-proof solenoid valves and limit switch boxes with ATEX certification are available for chemical, oil and gas applications.

Can the valve be operated manually if compressed air fails?

Yes. We recommend adding a handwheel override (manual gearbox) for DN100 and above. This allows operators to manually rotate the disc during air supply maintenance.

What is the lead time and MOQ?

MOQ is 1 piece. Standard configurations ship in 7–15 days. Custom actuator combinations (Ex-proof, positioner, special voltage) or large sizes take 25–35 days.

What is your warranty period?

We provide a 12-month warranty after shipment for material and manufacturing defects. This covers valve casting defects, disc / seat non-conformance, stem leakage, body dimensional non-conformance, actuator stroke failure and solenoid / limit switch non-conformance under rated air supply. Damage from misuse, lack of air filtration (no FRL installed), wrong fail-mode selection, over-torque adjustment or field disassembly by the customer is not covered. Always quote the valve serial number and heat number from the EN 10204 3.1 MTC when raising a warranty claim.

📚 Further reading:
• Electric vs Pneumatic Actuator: Which to Choose?
• Pneumatic Valve Actuators: A Complete Guide
• PN vs Class Pressure Rating: Quick Reference

You May Also Need

Request a Quote for This Pneumatic Wafer Butterfly Valve

Tell us the size, pressure and quantity you need. We reply within one working day.








    Need a Custom Valve or Fitting?

    Send us your specs: pressure, size, material and quantity. Our team will review the requirements and provide a direct quote.

    Southeast Asia: Indonesia, Malaysia, Thailand, Vietnam, Singapore, Philippines · Middle East: Saudi Arabia, UAE, Qatar, Kuwait, Oman, Bahrain · Other: the Americas, Europe, Africa, Australia

    FOB Ningbo / Shanghai · We usually reply within 24 business hours.

    Commercial terms: T/T 30% deposit + 70% before shipment, L/C at sight may be considered · export plywood case · 12 months warranty after shipment · EN 10204 3.1 MTC available on request · third-party inspection can be arranged on request.

    Disclaimer: This guide is for general engineering reference only. Final valve selection, sizing and installation must follow the manufacturer data sheet, the project P&ID and the applicable code (EN 1092, ASME B16.5, ASME B16.34, EN 10204 3.1). Where this article and those documents differ, the documents govern.