A wafer single plate check valve (also called tilting disc check valve) is the shortest check valve in our range — an ultra-compact, spring-assisted check valve that prevents backflow on HVAC chilled/condenser water circuits, cooling towers, pump stations and industrial piping. Its single tilting disc swings open under forward flow and snaps shut on reverse flow, minimizing water hammer.
Chuanglan manufactures wafer single plate check valves in CF8M (316) and CF8 (304) stainless steel as premium range. Ductile iron (GGG50) and cast iron (GG25) are standard for HVAC / water service. Sizes DN40–DN700 (NPS 1½″–28″), wafer body fits between DIN EN 1092-1 PN10/PN16 / ANSI B16.5 Class 150 / JIS 10K flanges. For tighter shutoff on large lines, compare our dual plate check valve; for steam and boiler feed, see lift check valve.
The key advantage of a single plate check valve is its ultra-compact body. Face-to-face is only 18–180 mm depending on size, compared to 16–75 mm for dual-plate wafer check valves and 150–1350 mm for flanged swing check valves. This makes it the ideal choice when you are retrofitting an existing pipeline where space is extremely tight — AHU plant rooms, ceiling voids, skid-mounted pump packages and equipment connections. We directly serve EPC contractors and valve distributors in Southeast Asia (Indonesia, Malaysia, Thailand, Vietnam) and the Middle East (Saudi Arabia, UAE, Qatar, Kuwait).
When selecting a single plate check valve, consider: size (DN40–DN700), pressure rating (PN10 / PN16 / ANSI 150#), body material (cast iron for water/HVAC, ductile iron for general, WCB for oil/gas, CF8M for corrosive service), seat material (NBR up to +80°C, EPDM up to +120°C for chilled water/HVAC, Viton up to +200°C for chemical/oil), spring stiffness (standard / low-cracking / anti-chatter), and flow direction. Always install a Y-strainer upstream to protect the tilting disc from welding slag and scale.
Southeast Asia & Middle East Market Notes
Thailand / Vietnam hotels, malls & hospitals HVAC: Ductile iron GGG50 body, EPDM seat, wafer single plate — standard for chilled water and condenser water circuits. The 18–55 mm face-to-face fits existing AHU and cooling tower connections during retrofits without changing pipe length.
Indonesia / Malaysia data centers & semiconductor fabs: Ductile iron body, NBR/EPDM seat, PN16 — used on chilled water primary/secondary pumps, CRAH connections and cooling return lines. Compact body fits in skid-mounted pump packages.
Saudi Arabia / UAE desalination & HVAC for high-rise towers: CF8M body, SS316 disc, Viton seat, ANSI 150# — used on SWRO brine return, cooling tower circulation and domestic water. Corrosion-resistant for coastal chloride environments.
Not sure whether single plate, dual-plate or swing check fits your line? Send us your pump flow rate, line size and available space.
Get Free Sizing Report →Single Plate vs Dual-Plate vs Swing vs Lift Check Valve
| Feature | Single Plate (This) | Dual-Plate / Butterfly | Swing | Lift |
|---|---|---|---|---|
| Face-to-face | 18–180 mm (shortest) | 16–75 mm (wafer) | 150–1350 mm | 130–750 mm |
| Closure speed | Very fast | <50 ms (fastest) | Slow (slam risk) | Medium |
| Pressure drop | Lowest | Low | Lowest | Highest |
| Shutoff tightness | Good | Better | Good | Best (metal/soft) |
| Handles solids | No | Limited | Yes | No (guides jam) |
| Orientation | Any | Any | Horizontal only | Horizontal only |
| Best size range | DN40–DN200 | DN40–DN700 | DN50–DN600+ | DN15–DN300 |
| Best for | HVAC retrofits, tight skids, AHU connections | Cooling water, pump discharge, water hammer | Large water, wastewater, slurry | Steam, boiler feed, high-pressure oil |
Technical Specifications
| Type | Wafer single plate / Tilting disc check |
| Size Range | DN40 – DN700 (NPS 1½” – 28″) |
| End Connection | Wafer type, fits between DIN EN 1092-1 PN10/PN16 / ANSI B16.5 Class 150 / JIS 10K flanges |
| Body Material | CF8M (316) / CF8 (304) — premium; WCB / GGG50 / GG25 on request |
| Disc | SS304 / SS316 tilting disc, NBR / EPDM / Viton soft seat |
| Spring | SS304 / SS316 stainless steel |
| Pressure Rating | PN10 / PN16 / ANSI Class 150 |
| Temperature Range | -10°C ~ +120°C (NBR) / -20°C ~ +120°C (EPDM) / up to +200°C (Viton) |
| Face-to-Face | 18–180 mm (shortest in check valve family) |
| Installation | Horizontal, vertical (up or down) or inclined |
| Applicable Media | Water, cooling water, HVAC, oil, gas, pump discharge lines |
| Testing | shell & seat pressure test per API 594 |
| Material Certificates | EN 10204 3.1 MTC (material test reports) included |
| Standard | API 594, EN 558, ISO 5752 |
Dimension Table — Wafer Single Plate PN16 (mm)
| DN | L (Face-to-Face) | D (OD) | D1 (Bolt Circle) | D2 (Disc) | H (Height) |
|---|---|---|---|---|---|
| 40 | 18 | 110 | 88 | 67 | 30 |
| 50 | 20 | 125 | 102 | 76 | 35 |
| 65 | 24 | 145 | 122 | 86 | 40 |
| 80 | 26 | 160 | 138 | 100 | 45 |
| 100 | 32 | 180 | 158 | 116 | 50 |
| 125 | 38 | 210 | 188 | 145 | 60 |
| 150 | 42 | 240 | 212 | 170 | 70 |
| 200 | 55 | 295 | 268 | 226 | 90 |
| 250 | 65 | 355 | 320 | 280 | 110 |
| 300 | 75 | 410 | 370 | 325 | 130 |
| 350 | 85 | 470 | 430 | 365 | 150 |
| 400 | 95 | 525 | 480 | 410 | 170 |
| 500 | 127 | 650 | 580 | 520 | 210 |
| 600 | 150 | 770 | 680 | 630 | 250 |
| 700 | 180 | 895 | 800 | 740 | 290 |
* PN10 drilled pattern available on request. ANSI Class 150 / JIS 10K flange drilling also available.
Worked Example: Replacing an Old Swing Check Valve on a DN80 Condenser Water Pump in Bangkok
Project: Retrofit of a 30-year-old office building in Bangkok, Thailand. DN80 condenser water pump discharge to cooling tower.
Problem: The existing flanged swing check valve (face-to-face 280 mm) is leaking and slamming on every pump trip. No room to expand the pipe — the pump skid is bolted to the floor, and 280 mm is already the maximum allowed between pump flange and tower header.
Step 1 — Confirm space available:
After removing the old swing check, the flange gap is still ~280 mm. A new flanged swing check would fit, but it slams. A wafer single plate DN80 has L = 26 mm — it fits easily, leaving 254 mm of pipe to re-use. No pipe cutting needed.
Step 2 — Confirm pump conditions:
Q = 80 m³/h, DN80 pipe. Velocity v = 80 / (3600 × 0.00503) = 4.4 m/s — a bit high for condenser water (target 2–3 m/s) but acceptable for a retrofit without changing pumps. Reverse flow on pump trip will slam a slow swing check; the spring-assisted single plate closes in ~0.1 s, preventing water hammer.
Step 3 — Material & seat:
Condenser water at 32–38°C, non-corrosive. Specify ductile iron GGG50 body, EPDM seat (best for cooling water up to +120°C, handles mild water treatment chemicals). No need for CF8M on budget retrofit.
Step 4 — Installation:
DIN EN 1092-1 PN16 flanges (D=200 mm, K=160 mm, 8×Φ18 bolt holes). Install wafer between the existing flanges using longer through-bolts. Add a Y-strainer upstream to catch rust scale from old pipework. Spring-loaded disc closes in any orientation — install horizontal.
4 Common Mistakes When Selecting Wafer Single Plate Check Valves
Mistake 1 — Using it on dirty water or sewage: The single tilting disc wedges open on rags, leaves or particulates, causing permanent leakage. For wastewater / palm oil effluent, choose a swing check valve — its disc swings fully out of the flow path.
Mistake 2 — Ignoring flow direction arrow: Every wafer check has a cast flow arrow. Installing backwards blocks the line — the disc can’t open. Verify arrow before tightening flange bolts.
Mistake 3 — Under-sizing for low flow: If minimum flow velocity is below 0.5 m/s, the spring may not fully open the disc, causing pressure drop and chatter. Tell us your minimum pump flow so we can fit a softer spring.
Mistake 4 — Forgetting a Y-strainer: Welding slag, Teflon tape and pipe scale score the soft seat. Always install a Y-strainer upstream — it costs 1/10 of the valve and doubles seat life.
Need Sizing Help or a Quote?
Send size (DN), pressure (PN/ANSI), material (304/316L), seat (EPDM/Viton) and quantity — we reply within 24 hours.
Get Free Quote »Applications
HVAC & Cooling: Chilled water, condenser water, cooling tower circulation, AHU connections.
Data Centers: CRAH unit return, primary/secondary chilled water pumps, skid packages.
Water & Wastewater: Building domestic water, fire water mains (clean service only).
Oil & Chemical: Hydraulic oil, cooling oil circuits (NBR / Viton seat).
Commercial Terms & Shipping
Payment: T/T 30% deposit + 70% before shipment; L/C at sight accepted for orders above USD 20,000. PayPal for sample orders.
Warranty: 12 months after shipment for material and manufacturing defects. Covers casting defects, seal leakage and material non-conformance. Damage from misuse, improper installation or corrosion beyond specified limits is not covered.
Packaging: Export plywood case (fumigation-free) or seaworthy pallet. Suitable for FCL container and LCL consolidation.
Shipping Documents: EN 10204 3.1 MTC, pressure test certificate, packing list, commercial invoice. Certificate of origin and BL available on request.
Shipment Port: FOB Ningbo / Shanghai, China. Can also arrange CIF / DAP to your destination port.
Third-Party Inspection: SGS, Bureau Veritas or Intertek pre-shipment inspection supported at your cost.
FAQ
Single plate vs dual plate wafer check valve — which should I pick?
Single plate (tilting disc) has the shortest face-to-face (18–180 mm) and lowest pressure drop, ideal for space-constrained HVAC and pump discharge. Dual plate gives tighter shutoff and handles higher reverse pressure, better for large lines (DN300+) and water hammer protection. For DN40–DN200 single plate is the common choice; DN250+ we usually recommend dual plate.
Why is the body so short — can it still handle pressure?
Yes. The short body is a wafer pattern clamped between two standard flanges — the flange bolts carry the line pressure, not the valve body itself. Pressure rating is PN16 / ANSI 150# just like a full flanged valve; only the face-to-face length is reduced.
Does it work on vertical pipe (flow going up)?
Yes. The spring-assisted disc closes mechanically, independent of gravity. Single plate wafer check valves work in horizontal, vertical-up, vertical-down and inclined orientations — a key advantage over flanged swing and lift check valves which require horizontal mounting.
Can it handle sewage or wastewater with solids?
We do not recommend it for wastewater with solids, rags or fibers — the tilting disc can wedge open on debris. For sewage, choose a flanged swing check valve. Clean water, HVAC cooling water, oil and gas are fine.
What cracking pressure should I expect?
Standard spring cracking pressure is ~0.05–0.1 bar (0.7–1.5 psi). For very low flow systems we can fit a softer spring; for high-vibration applications a stiffer spring prevents chattering. Tell us your minimum flow velocity.
What is the difference between this and a tilting disc check valve?
They are the same product. “Single plate”, “tilting disc”, “wafer tilting” and “single leaf” are all industry names for the same wafer-pattern check valve with one hinged disc. Some manufacturers call it “wafer tilting disc”, others “single plate”.
MOQ, stock and delivery time?
MOQ is 1 piece. DN40–DN200 in cast iron / ductile iron are usually in stock (7 days). DN250 and above, WCB carbon steel or CF8M stainless takes 15–30 days. ANSI 150# / JIS 10K flange drilling available on request.
What is the warranty period for your valves?
We provide a 12-month warranty after shipment for material and manufacturing defects. This covers casting defects, seal leakage and material non-conformance. Damage from misuse, improper installation or corrosion beyond specified limits is not covered.
📚 Further reading:
• Wafer Check Valve vs Swing Check Valve (2026 Guide)
• How to Select a Wafer Butterfly Valve for Seawater Service
• Butterfly Valve Selection Guide (Size, Pressure, Material)